R32 Inverter Air Source Heat Pump
video
R32 Inverter Air Source Heat Pump

R32 Inverter Air Source Heat Pump

Featuring a DC inverter system, our R32 split inverter heat pump runs at optimal efficiency thanks to refined energy-saving control software. Capable of producing hot water up to 60°C, it fulfills residential heating and cooling demands. The unit works stably at ambient temperatures between -25°C and 43°C. Widely exported across Europe, our split heat pump performs excellently in cold areas like Northern and Eastern Europe and greatly mitigates freezing risks.

Our R32 split inverter heat pump adopts a DC inverter system. Optimized energy efficiency control software allows the unit to run with maximum energy savings. This R32 heat pump can deliver hot water up to 60°C and provides space heating & cooling for buildings. It operates reliably within an ambient temperature range of -25°C to 43°C.We have supplied units to numerous European markets. Particularly suited for low-climate regions including Eastern and Northern Europe, our split-type inverter heat pump effectively lowers the risk of freezing.

Dc Heat Pump Parameters

 

K-Thermal DC Inverter air to water heat pump for Heating & Cooling & Hot Water (Split type, R32 )

Model

DCI03PS-H3DS

DCI05PS-H5DS

DCI06PS-H5DS

DCI08P-H8DS

Power supply

V/ Hz

220V/50Hz

380V/50Hz

Dry/Wet bulb: 7/6℃; Water inlet/outlet: 35/40℃

Heating capacity

kW

10.50

14.71

16.23

20.20

Input power

kW

2.15

3.13

3.51

4.33

COP

/

4.88

4.70

4.63

4.66

Dry/Wet bulb: 7/6℃; Water inlet/outlet: 45/50℃

Heating capacity

kW

10.60

14.89

15.97

20.00

Input power

kW

2.79

4.01

4.63

6.05

COP

/

3.80

3.71

3.45

3.31

Dry/Wet bulb: 7/6℃; Water inlet/outlet: 47/55℃

Heating capacity

kW

10.15

13.60

15.25

19.64

Input power

kW

3.39

4.26

5.00

6.34

COP

/

2.99

3.19

3.05

3.10

Dry/Wet bulb: -7/-8℃; Water inlet/outlet: 30/35℃

Heating capacity

kW

7.58

12.12

14.48

16.51

Input power

kW

2.32

3.66

4.52

5.25

COP

/

3.27

3.32

3.20

3.15

Dry/Wet bulb: -20/-21℃; Water inlet/outlet: 30/35℃

Heating capacity

kW

4.51

7.32

8.47

10.45

Input power

kW

2.19

3.26

3.85

4.85

COP

/

2.06

2.25

2.20

2.16

Dry/Wet bulb: 35/24℃; Water inlet/outlet: 23/18℃

Cooling capacity

kW

10.40

14.93

16.17

20.17

Input power

kW

2.35

3.51

4.10

5.03

EER

/

4.43

4.25

3.94

4.01

Dry/Wet bulb: 35/24℃; Water inlet/outlet: 12/7℃

Cooling capacity

kW

8.46

12.83

14.06

18.10

Input power

kW

2.88

4.49

4.97

6.43

EER

/

2.93

2.86

2.83

2.81

Seasonal Heating Energy Efficiency Rating

LWT at 35℃

A+++

A+++

A+++

A+++

LWT at 55℃

A++

A++

A++

A++

SCOP

LWT at 35℃

4.55

4.64

4.70

4.64

LWT at 55℃

3.55

3.58

3.65

3.43

SEER

LWT at 7℃

4.66

4.67

4.62

4.65

LWT at 18℃

6.58

6.85

6.74

6.76

Max. Current

A

14.10+13.60+13.60+13.60

30+13.60+13.60+13.60

30+13.60+13.60+13.60

15+13.60+13.60+13.60

Rated Current

A

10+13.60+13.60+13.60

14+13.60+13.60+13.60

15+13.60+13.60+13.60

8+13.60+13.60+13.60

Water pressure drop

kPa

40.00

42.00

44.00

46.00

System pressure

Mpa

1/4.15

Refrigerant

Type

R32

R32

R32

R32

Quantity

kg

2.50

2.90

3.50

4.00

GWP value

675.00

675.00

675.00

675.00

Equivalent CO2

Ton

1.69

1.96

2.36

2.70

Fan motor

Type

DC INVERTER

Quantity

1.00

2.00

2.00

2.00

Noise level(Outdoor unit)

dB(A)

57.00

62.00

62.00

68.00

Noise level(Indoor unit)

dB(A)

35.00

35.00

35.00

35.00

Waterproof level

IPX4

Refrigerant pipe between indoor and outdoor unit

Gas pipe

mm

φ15.88

φ15.88

φ15.88

φ19

Liquid pipe

mm

φ9.52

φ9.52

φ9.52

φ9.52

Water pipe connection

Inlet

mm

DN25

DN25

DN25

DN32

Outlet

mm

DN25

DN25

DN25

DN32

Outdoor unit dimensions

mm

1160x490x860

1160x490x1260

1160x490x1260

1160x490x1568

Outdoor unit pacakge dimensions

mm

1195x500x1010

1195x500x1410

1195x500x1410

1195x500x1718

Indoor unit dimensions

mm

530*770*340

530*770*340

530*770*340

530*770*340

Indoor unit pacakge dimensions

mm

570*790*400

570*790*400

570*790*400

570*790*400

Outdoor unit Net Weight

kg

60

90

100

120

Indoor unit Net Weight

kg

33.5

35

36

38

Loading(20GP/40HQ)

Pcs

32/76

21/44

21/44

21/44

The above parameters may have some differences from the final product because of products updating, so above information is not the provision of any business contract. Please refer to final product label when buy, or refer to us for any information. Our company keeps the right to interpret.

R32
 

 

Adopting the new R32 refrigerant with zero ODP and a GWP value of 675, our units help cut greenhouse gas emissions for sustainable development.

 

 

Our heat pumps support WiFi connectivity. You can conveniently control the unit via our custom-developed dedicated App.

R-C
202209151337031
 

 

High-precision electronic expansion valve: The unit adopts an electronic expansion valve with 500-step regulation. It precisely adjusts the superheat degree to ensure the system operates with high efficiency.

 

 

Energy efficiency class A+++ for heating mode at a supply water temperature of 35°C.

Energy efficiency class A++ for heating mode at a supply water temperature of 55°C.

class-energy-efficiency-of-washing-machines

 

 

 

Hot Tags: r32 inverter air source heat pump, China r32 inverter air source heat pump manufacturers, suppliers, factory, DC Inverter, Hvac Inverter Heat Pump, R32 Air To Water, R32 Inverter Heat Pump, Split Heat Pump, Whole House Inverter Heat Pump

Send Inquiry